You can check for a floating neutral by finding 2 different phases (a 240V outlet for a stove, dryer, welder, AC unit, etc is a convenient place to measure) and checking neutral to ground on each phase. Both phases should have close to the same voltage.
Over 146V is nuts and shouldn't happen on a 120V circuit.